The Fluke 87V Industrial Multimeter provides the resolution and accuracy to efficiently troubleshoot motor drives, plant automation, power distribution, and electromechanical equipment even in loud, high-energy, and high-altitude locations. A low pass filter supports accurate frequency measurements on VFDs and captures intermittents as fast 250 µS.

Use the 87V to measure AC current up to 10 A directly, or use an optional clamp for high current measurements, frequency to 200 kHz, plus % duty cycle, resistance, continuity and diode test. And it includes a built-in thermometer so you can take temperature readings without having to carry a separate instrument, and more. Plus, with its bright, two-level backlit display you’ll be able to see the results better in dim light.

Features:

  • Rugged, high accuracy industrial multimeter to measure current, voltage and frequency on complex variable frequency drive (VFD) signals
  • Offers true-RMS AC voltage and current for measuring non-linear signals
  • Captures intermittents as short as 250 µS
  • Safety rated CAT III 1000 V, CAT IV 600 V
  • Includes a built-in thermometer and temperature probe

Specifications:

  • Voltage DC
    • Maximum voltage: 1000 V
    • Accuracy: ±(0.05% + 1)
    • Maximum resolution: 10 µV
  • Voltage AC
    • Maximum voltage: 1000 V
    • Accuracy: ±(0.7% + 2) True RMS
    • AC bandwidth: 20 kHz with low pass filter; 3 dB @ 1 kHz
    • Maximum: resolution 0.1 mV
  • Current DC
    • Maximum amps: 10 A (20 A for 30 seconds maximum)
    • Amps accuracy: ±(0.2% + 2)
    • Maximum resolution: 0.01 µA
  • Current AC
    • Maximum amps: 10 A (20 A for 30 seconds maximum)
    • Amps accuracy: ±(1.0% + 2) True RMS
    • Maximum resolution: 0.1 µA
  • Resistance
    • Maximum resistance: 50 MΩ
    • Accuracy: ±(0.2% + 1)
    • Maximum resolution: 0.1 Ω
  • Capacitance
    • Maximum capacitance: 9,999 µF
    • accuracy: ±(1% + 2)
    • Maximum resolution: 0.01 nF
  • Frequency
    • Maximum frequency: 200 kHz
    • Accuracy: ±(0.005% + 1)
    • Maximum resolution: 0.01 Hz
  • Duty cycle
    • Maximum duty cycle: 99.9%
    • Accuracy: ±(0.2% per kHz + 0.1%)
    • Maximum resolution: 0.1%
  • Temperature measurement:
      • –200.0 °C – 1090 °C
      • –328.0 °F – 1994.0 °F
      • excluding probe
  • 80 BK temperature probe:
    • –40.0 °C – 260 °C
    • –40.0 °F – 500 °F, 2.2 °C or 2% whichever is greater
  • Conductance
    • Maximum conductance: 60.00 nS
    • Accuracy: ±(1.0% + 10)
    • Maximum resolution: 0.01 nS
  • Diode
    • Range: 3 V
    • Resolution: 1 mV
    • Accuracy: ±(2% + 1)
  • Duty cycle range:
    • Accuracy Within ±(0.2% per kHz + 0.1%)
  • Environmental Specifications
    • Operating temperature: –20 °C to + 55 °C
    • Storage temperature: –40 °C to + 60 °C
    • Humidity (without condensation):
      • 0% – 90% (0 °C – 35 °C)
      • 0% – 70% (35 °C – 55 °C)
    • Operating Altitude: 2000 m
  • Safety Specifications
    • Overvoltage category: EN 61010–1 to 1000 V CAT III, 600V CAT IV
    • Agency approvals: CE, CSA, RCM
  • Size: 201 x 98 x 52 mm (with holster)
  • Weight:
    • 355 g
    • 624 g – with holster
  • Display:
    • Digital:
      • 6000 counts updates 4/sec.
      • 19,999 counts in high–resolution mode
    • Analog: 32 segments, updates 40/sec
    • Frequency: 19,999 counts, updates 3/sec at > 10 Hz
  • Warranty: Lifetime
  • Battery Life Alkaline: ~400 hours typical, without backlight
  • Shock: 1 Meter drop per IEC 61010–1:2001
  • Vibration: Per MIL–PRF–28800 for a Class 2 instrument

Includes:

  • TL75 Test Leads
  • AC175 Alligator Clips
  • Holster
  • 9V Battery (Installed)
  • 80BK Temperature Probe